天然气门站一起Q235B输气管线焊接事故分析
Issue Number
Issue 06, 2012
[View other articles in this issue]
DOI
Receiving Time
Revision Time
Publish Date
Publication Date
2012.06.15
Manuscript ID
Author
刘 伟
Organization
章丘市天然气有限责任公司
Abstract
本文介绍了天然气门站一起Q235B输气管线延迟裂纹事故。分析了裂纹漏检和产生原因,强调
慎用高强度级别、纤维素型下向焊进口焊条和焊完24小时后探伤检查的必要性。本文还指出:
这次事故是在试验压力略高于设计压力1.5倍时发生的,当试验压力较小时,可能不会出现类似
事故,但并不等于不存在延迟裂纹这一隐患,它有可能在使用中扩展,导致泄漏,希望已经投
用的类似管线加强在役检验。