Abstract

通过交流电位梯度法(A字架)和人体电容法分析和比较,得出人体电容法适合城市燃气管网防腐层检测;运用此法检测惠州燃气管网并进行开挖验证,开挖验证准确率100%;在检测和验证过程中发现以下问题,受检管道与其他管道净距不符规范、受检管道敷设埋深不合理、受检管道安装牺牲阳极不科学、部分管道欠阴极保护效果,并对以上问题给出积极建议。